| How it shows the level | The liquid in a glass tube between two gauge valves, usually behind a guard | One flat glass with prism grooves: the liquid shows dark, the vapour space bright | The liquid between two flat glasses, viewed through the gauge | Flags outside a sealed chamber, turned by the float's magnet: red below the level, white above |
| Pressure boundary | The glass tube, sealed at each end | Glass and gasket under a bolted cover, on every section | Two glasses and gaskets under bolted covers, on every section | One welded 316 chamber (Magnamont™, Fortimag™) or bonded CPVC or PVDF chamber (Polysight™). No glass |
| Pressure | Low-pressure service | Set by the glass size, construction and temperature; falls as temperature rises | Set by the glass size, construction and temperature; falls as temperature rises | Full vacuum to 5,000 psig (345 bar) Fortimag™, 3,400 psig (234 bar) Magnamont™, 150 psig (10 bar) Polysight™ |
| Temperature | Limited by the tube and its seals | Limited by the glass and gaskets; hot water and steam etch the glass | Limited by the glass and gaskets; mica shields protect the glass in hot water and steam | −40 to +842 °F (−40 to +450 °C) Magnamont™ and Fortimag™, lower temperatures on application review; −4 to +248 °F (−20 to +120 °C) Polysight™ |
| Visible range | Short lengths | Built in sections; blind lengths between sections unless gauges overlap | Built in sections; blind lengths between sections unless gauges overlap | One chamber, standard to 18.5 ft (222 in, 5,640 mm) C-C; longer lengths on request |
| Reading | Close up | Close up, with light on the glass | Close up, often with an illuminator behind the gauge | High-contrast flags, readable from across the plant |
| What is seen | The liquid itself | The liquid surface, in clean, clear liquids | The liquid itself: colour, clarity and layers | The level only. Interface service with a float set for the second liquid (option INT) |
| Upkeep | Cleaning; tube and seal replacement | Cleaning; glass and gasket replacement once etched or stained | Cleaning; glass, gasket and mica shield replacement | Indicator not in contact with the process; chamber flushed through the drain |
| Alarms and signal | Separate instruments, often on separate nozzles | Separate instruments, often on separate nozzles | Separate instruments, often on separate nozzles | SurePoint™ SPDT clamp-on switches and a LevelSync™ 4–20 mA transmitter on the same chamber |