Lamont Controls 1-833-7LAMONT Request a quotation Call

Cookies on this site

Analytics, advertising cookies (including our ads on other sites) and session recording stay off unless you accept. These tools show how the site is used and which advertising brings enquiries, and let Google and Microsoft show our ads to past visitors on other sites. The choice can be changed at any time under Cookie settings at the foot of each page. Privacy policy

Photo of a top-mount float switch: black cover and green housing collar above a stainless process flange, with a stainless stem and a stainless ball float below
Photo
Top-mount float switch

SnapTrip™ Float and displacer level switches

SnapTrip™ is a range of flanged float and displacer level switches for high and low level alarms on tanks and vessels, in three models: side-mount float, top-mount float and top-mount displacer. Wetted parts and the process flange are 316L stainless steel. The contact is a snap-action micro switch, DPDT or SPDT, in a weatherproof housing.

Wetted parts
316L SSflange in 316L; forged flange on request
Process connection
Class 150 RF2, 3 or 4 in, by model
Contact rating, to
15 Aat 250 VAC; DPDT or SPDT, by model
Process temperature, to
248 °F120 °C; operating pressure to 142 psig

Weatherproof housings, IP65 or IP66 · ambient from −4 °F (−20 °C)

Product

Side-mount and top-mount switches

Photograph of a side-mount float switch with a 2 in flange: cylindrical stainless float on its arm, the flange, and the switch housing with its cable entry
Side-mount float switch
Photograph of a top-mount float switch: switch housing above the top flange, with a spherical stainless float on a stem below the flange
Top-mount float switch
Photograph of a top-mount displacer switch: switch housing above the top flange, with a cylindrical stainless displacer hung on its suspension below the flange
Top-mount displacer switch

Photographs, representative units. Nameplate and finish as supplied may differ.

Operation

Principle of operation

Render of a tank cut away to show the three switches: a top-mount float switch with its float above the liquid, a top-mount displacer switch with its displacer hung in the liquid, and a side-mount float switch with its float inside the tank wall
Render: top-mount float, top-mount displacer and side-mount float switches on one tank.

Float switch. A float rides on the liquid. When the level reaches the switch point, the movement of the float operates a snap-action micro switch in the housing, outside the process. The side-mount switch is fitted at the alarm height; the top-mount switch hangs its float below the flange at the switch point.

Displacer switch. A displacer hangs below the switch head at the switch point. As the liquid covers the displacer, its apparent weight falls and the switch operates. The suspension length sets the switch point, so a switch on a top nozzle can alarm low in a deep vessel.

Typical uses

Level alarms
High and low level alarms on storage tanks, day tanks and process vessels
Pumps and valves
A dry contact to the plant control system to start or stop a pump or open a valve
Deep tanks and sumps
A top-mount displacer switch places the switch point low in a vessel with no side nozzle
Magnetic level gauges
SurePoint™ clamp-on switches mount on the gauge chamber and need no process connection

Product

Models

Render of a side-mount float switch bolted to a flanged nozzle on a tank wall, the tank cut away to show the float inside at the liquid surface
Render · 2 in Class 150 RF, vessel wall

SN-100 side-mount float switch

Mounts in a flanged nozzle on the vessel wall at the alarm height. A 2 in Class 150 RF flange with a 41 mm float, which passes a 2 in Schedule 40 or 80 nozzle. One DPDT micro switch rated 10 A at 250 VAC.

Render of a top-mount float switch bolted to a flanged nozzle on a tank roof, the tank cut away to show the float on its stem below the roof
Render · 4 in Class 150 RF, vessel top

SN-200 top-mount float switch

Mounts on a 4 in Class 150 RF nozzle on the vessel top, with a 90 mm float. The switch point is 300 mm (11.8 in) below the flange as standard. One SPDT micro switch rated 15 A at 250 VAC.

Render of a top-mount displacer switch bolted to a flanged nozzle on a tank roof, the tank cut away to show the displacer hung on its suspension in the liquid
Render · 3 in Class 150 RF, vessel top

SN-300 top-mount displacer switch

Mounts on a 3 in Class 150 RF nozzle on the vessel top. A 76.3 mm displacer hangs at the switch point on a standard suspension length of 2,000 mm (78.7 in). One SPDT micro switch rated 15 A at 250 VAC.

On a magnetic level gauge. For alarm points on a Lamont magnetic level gauge, SurePoint™ clamp-on switches mount outside the gauge chamber and need no process connection.

Options

Options and ordering

  • Forged flange F

    Forged 316L flange (ASTM A182) in place of the standard 316L plate flange (ASTM A240). Longer material lead time.

  • Insertion length SN-100

    185 mm standard. Longer to suit the nozzle, on request.

  • Switch point SN-200

    300 mm (11.8 in) below the flange, standard.

  • Suspension length SN-300

    2,000 mm (78.7 in) standard; the switch point is set to the order.

  • Alarm action H · L

    High or low level alarm, stated for each SN-300 displacer switch.

Ordering code

  1. SN-x00
  2. Connection
  3. Flange
  4. Length
  5. Action
PositionCodeDescription
ModelSN-100SnapTrip™ side-mount float switch, 1 × DPDT
SN-200SnapTrip™ top-mount float switch, 1 × SPDT
SN-300SnapTrip™ top-mount displacer switch, 1 × SPDT
Connection20 · 40 · 302 in (SN-100) · 4 in (SN-200) · 3 in (SN-300), Class 150 RF
FlangeP · F316L plate, ASTM A240 (standard) · 316L forged, ASTM A182
LengthmmInsertion (SN-100), switch point below the flange (SN-200) or suspension length (SN-300)
ActionH · LHigh or low level alarm (SN-300)

Example: SN-300-30-P-2000-L. Fluid, specific gravity, operating pressure and temperature are stated on the order datasheet, not in the model code.

Data

Technical specifications

Standard construction · confirmed on each quotation
SpecificationSide-mount float switchTop-mount float switchTop-mount displacer switch
MountingSide, in a nozzle on the vessel wallTopTop
Process connection2 in Class 150 RF flange4 in Class 150 RF flange3 in Class 150 RF flange
Flange material316L stainless steel plate (ASTM A240); forged 316L (ASTM A182) on request
Wetted parts316L stainless steel
Float or displacerFloat 41 × 100 mmFloat, 90 mmDisplacer 76.3 × 150 mm
LengthInsertion 185 mm; longer to suit the nozzle on requestSwitch point 300 mm (11.8 in) below the flange, standardSuspension 2,000 mm (78.7 in), standard; switch point to order
SwitchSnap-action micro switch, 1 × DPDTSnap-action micro switch, 1 × SPDTSnap-action micro switch, 1 × SPDT
Contact rating10 A at 250 VAC; 5 A at 30 VDC15 A at 250 VAC; 0.5 A at 125 VDC15 A at 250 VAC; 0.5 A at 125 VDC
EnclosureWeatherproof, IP66Weatherproof, IP65Weatherproof, IP65
HousingAluminumCarbon steel and aluminumCarbon steel and aluminum
Cable entry½ in NPT (F), by adapter¾ in NPT (F), by adapter¾ in NPT (F), by adapter
Process temperature, max.248 °F (120 °C)
Operating pressure, max.142 psig (9.8 bar)
Ambient temperature−4 to 140 °F (−20 to 60 °C)−4 to 176 °F (−20 to 80 °C)−4 to 176 °F (−20 to 80 °C)
Specific gravityConfirmed for each order from the fluid data
LocationOrdinary (non-hazardous) locations

Nozzle bore. The float or displacer passes through the process nozzle, so the nozzle bore must be larger than it: 41 mm for the side-mount switch, 76.3 mm for the displacer and 90 mm for the top-mount float. Send the nozzle size and schedule with the request.

Service. For ordinary (non-hazardous) locations. Not for use as a boiler low-water cut-off or in a safety instrumented function.

Selection

Selection by nozzle and switch point

SwitchSuitsConsider
Side-mount float switch2 in nozzleA flanged nozzle on the vessel wall at the alarm height.One nozzle for each alarm point. The float must pass the nozzle bore.
Top-mount float switch4 in nozzleA high level alarm near the vessel top, where no side nozzle is available.One switch point, 300 mm (11.8 in) below the flange as standard.
Top-mount displacer switch3 in nozzleA switch point low in a deep tank or sump, from a nozzle on the vessel top.The suspension length and switch point are set to the vessel. State high or low alarm.
SurePoint™ clamp-on switchOn a magnetic level gaugeAlarm points on a Lamont magnetic level gauge.Mounts outside the gauge chamber, with no process connection. SurePoint™

Enquiry

What to send for a quotation

A complete request is quoted fastest. Send the available details; Lamont Controls Engineering will ask for the rest.

  1. Switch type and quantitySide-mount float, top-mount float or top-mount displacer.
  2. NozzleSize, flange class and pipe schedule, so the float or displacer passes the bore.
  3. Process conditionsFluid, specific gravity, operating pressure and temperature.
  4. Alarm action and switch pointHigh or low for each switch, and the depth below the flange for top-mount switches.
  5. Electrical loadThe voltage and current the contact switches.
  6. Tag numbers and required dateOne request can cover several switches; give each a tag number.

Upload your datasheets and drawings with the request

Quotation

Request a quotation

Complete the fields below, or attach the datasheet, requisition or tag list: with a file attached, the switch fields are optional. Fields marked * are required for pricing.

For several switches, send one request with a tag number for each, or attach the tag list. For a general enquiry, select Quick message.

What happens nextLamont Controls Engineering reviews the request and replies with a quotation.

1-833-7LAMONT info@lamontcontrols.com

Provide your contact details and a brief message. Lamont Controls Engineering will follow up.

Attach the datasheet, requisition or tag list and enter your contact details. Lamont Controls Engineering takes the process data from the file.

A datasheet, requisition or tag list can replace the switch fields: attach it and they become optional.

Contact

Lamont Controls Engineering reviews every request.By sending this form you agree to the Terms of use. See the Privacy policy.

Questions

SnapTrip questions

Which models are in the SnapTrip™ range?

Three flanged switches for high and low level alarms: the SN-100 side-mount float switch on a 2 in Class 150 RF nozzle, the SN-200 top-mount float switch on a 4 in nozzle and the SN-300 top-mount displacer switch on a 3 in nozzle. Wetted parts are 316L stainless steel. For alarm points on a Lamont magnetic level gauge, SurePoint™ clamp-on switches mount on the gauge chamber instead.

What is the difference between a float switch and a displacer switch?

A float switch operates when the float, riding on the liquid, reaches the switch point. A displacer switch hangs a displacer at the switch point; as the liquid covers it, its apparent weight falls and the switch operates. Hung from a top nozzle on a standard suspension length of 2,000 mm (78.7 in), a displacer places the switch point low in a deep vessel.

What contact does the switch provide?

A snap-action micro switch. The side-mount float switch has one DPDT contact rated 10 A at 250 VAC and 5 A at 30 VDC. The top-mount float and displacer switches have one SPDT contact rated 15 A at 250 VAC and 0.5 A at 125 VDC.

Will the float pass through the nozzle?

The float or displacer passes through the process nozzle, so the nozzle bore must be larger than it: 41 mm for the side-mount switch, 76.3 mm for the displacer and 90 mm for the top-mount float. Send the nozzle size and schedule with the request.

What should a request include?

The switch type and quantity, the nozzle size, flange class and schedule, the fluid, specific gravity, operating pressure and temperature, high or low alarm for each switch with the switch point, and the electrical load. Lamont Controls Engineering replies with a quotation.

Downloads

Documentation

Document access

Enter your business email address to download the technical specification sheet.

Your email address is used for communications related to this request. You may unsubscribe at any time. Lamont Controls Inc., 800–120 Eglinton Ave E, Toronto, ON M4P 1E2, Canada · info@lamontcontrols.com.

Cover of SN-TS-011, SnapTrip technical specification sheet, November 2026SN-TS-011 · NOVEMBER 2026Technical specification sheet2 pages · 306 KB PDFDownload

In this sheet

  • Page 1. Overview, key figures, highlights and benefits.
  • Page 2. Technical specifications: principle, models, process connections, materials, float and displacer, switch and contact rating, enclosure, temperature and pressure, options and ordering code.

Drawings. Sales drawings are sent on request, after review. The approval drawing is issued after the purchase order.

Request a quotation Call