Analytics, advertising cookies (including our ads on other sites) and session recording stay off unless you accept. These tools show how the site is used and which advertising brings enquiries, and let Google and Microsoft show our ads to past visitors on other sites. The choice can be changed at any time under Cookie settings at the foot of each page. Privacy policy

Render of a magnetic level gauge with guided wave radar: a 3 in stainless standpipe with the radar transmitter on its top flange, and a magnetic level gauge on its own valved connections beside it
Render
Gauge and radar on one bridle

GWR Magnetic level gauge with guided wave radar

A Lamont magnetic level gauge with a guided wave radar (GWR) transmitter in its own chamber beside it, supplied as one assembly. The gauge reads locally with no power; the radar sends a 4–20 mA level signal with HART® to the control system. Two measurements on one vessel, on two different principles.

Radar accuracy
±2 mm±0.08 in; repeatability ±1 mm
Output
4–20 mAwith HART®, two-wire; fieldbus on request
Probe length, to
19.7 ft6 m rod probe; cable probe for longer chambers
Process temperature, to
392 °F200 °C with a temperature adapter; 302 °F (150 °C) standard

Gauge: Magnamont™ or Fortimag™ · radar: the standard transmitter Lamont supplies, or your plant's make

Operation

Principle of operation

Render of a radar chamber in half-section: the guided wave radar transmitter on the top flange, the rigid probe running down the centre of the 3 in chamber with a centring disc, flanged side connections with a gate valve on each vessel nozzle, and a valved vent and drain
Render: radar chamber in half-section, with the probe and centring disc.

Magnetic level gauge. A float in the gauge chamber carries a magnet. As the level moves, the float turns the bicolour flags of the indicator outside the chamber, so the level reads at the vessel with no power. Alarm switches can clamp to the chamber.

Guided wave radar. A high-frequency microwave pulse runs down a probe from the transmitter head and reflects from the liquid surface. The time of flight gives the level, sent as a 4–20 mA signal with HART®. The reading does not depend on the fluid's density, and the probe has no moving parts.

Two chambers, two readings. The probe sits in its own chamber, clear of the float. A float held up by deposits, or a coated probe, affects one reading, not both, and the two can be compared. With isolation valves, the radar chamber can be shut off and the transmitter removed while the gauge stays in service.

Typical uses

Two principles
A local reading and a control-system signal from float buoyancy and radar time of flight
Separators
Total level and the oil-water interface from the radar, where the two liquids separate cleanly, with the gauge showing the level at the vessel
Changing density
The radar reading does not depend on specific gravity, where the fluid or its temperature varies
Plant standards
The radar make the plant has standardized on, with a Lamont gauge beside it

Product

Configurations

Render of the instrument bridle at an angle: the radar on the top flange of the 3 in standpipe, the magnetic level gauge on its own valved connections, and a gate valve on the vessel nozzle
Render · gauge and radar on one bridle

On one bridle

A 3 in standpipe on the vessel nozzles carries the radar on its top flange. The gauge mounts on the standpipe's own valved connections, so one pair of vessel nozzles serves both instruments, with isolation valves and a valved vent and drain as on a Lamont level bridle.

Render of an external radar chamber seen from outside at an angle: the radar on the top flange, flanged side connections with a gate valve on each vessel nozzle, and a valved vent and drain
Render · radar in its own chamber

Radar in its own chamber

The radar in an external chamber on its own pair of vessel nozzles, beside the gauge on its nozzles. For vessels with two pairs of nozzles.

The gauge. Magnamont™ for most process service, Fortimag™ for extreme pressure. Gauge ratings, materials and indicator options are on each gauge's page.

Data

Technical specifications

Standard radar transmitter · confirmed on each quotation
SpecificationStandard
AssemblyMagnetic level gauge and guided wave radar transmitter, the radar in a separate chamber
GaugeMagnamont™ or Fortimag™, to the gauge's own specification
Radar chamber3 in 316 stainless steel standpipe
Radar connection3 in Class 150 RF flange, 316/316L; other classes on request
Vessel connectionsFlanged, to the vessel nozzles; size and class to order
Design pressure and temperaturePer job, stated on the approval drawing
Measuring principleGuided wave radar (time-domain reflectometry)
Probe316L rod, 8 mm, to 19.7 ft (6 m); cable probe with a centring weight for longer chambers
Radar wetted parts316L and PEEK; FKM or FFKM seal to suit the fluid
Measuring rangeThe probe length less the blocking distances at its top and bottom; the chamber is sized so the range between the vessel nozzles is covered
Accuracy±2 mm (±0.08 in) on level, outside the blocking distances; interface ±5 mm (±0.2 in) typical
Repeatability±1 mm (±0.04 in) or better
Dielectric constant, min.1.6
InterfaceTotal level and interface, with a non-conductive upper liquid at least 100 mm (4 in) thick over a liquid whose dielectric constant is at least 10 higher, such as water
Process temperatureTo 302 °F (150 °C) standard; to 392 °F (200 °C) with a temperature adapter. Lower limit −40 to −4 °F (−40 to −20 °C), set by the seal material
Process pressureRadar: full vacuum to 580 psig (−1 to 40 bar), limited by its flange: 275 psig (19 bar) with the standard Class 150 flange. The assembly's rating is set by the flange class and the gauge, and confirmed on each quotation
Output4–20 mA with HART®, two-wire; Profibus PA, Foundation Fieldbus or Modbus on request
Supply9.6 to 35 VDC, loop powered
HousingAluminum or 316L stainless steel; IP66/IP68 (0.2 bar)
Cable entry½ in NPT
Display and setupDisplay and adjustment module on the transmitter, Bluetooth on request; setup by HART® or PC software
Ambient temperature−40 to 176 °F (−40 to 80 °C)
Hazardous locationsExplosion-proof and intrinsically safe transmitter versions, with CSA, FM, ATEX or IECEx approval, on request
Functional safetySIL 2 qualified transmitter version on request

Radar make. The figures above are for the standard transmitter Lamont supplies. With the plant's own make, the radar data follow that transmitter, and Lamont sizes the chamber and top flange to it.

Pressure test. The chambers are pressure tested before shipment, without the transmitter fitted.

Options

Options

  • Plant-standard radar

    The make the plant has standardized on, in place of the standard transmitter. Lamont sizes the chamber and the top flange to it.

  • Hazardous locations

    An explosion-proof or intrinsically safe transmitter, to the area classification on the request.

  • Interface measurement

    Total level and the interface from one radar, for a non-conductive liquid over water.

  • Fieldbus output

    Profibus PA, Foundation Fieldbus or Modbus in place of 4–20 mA with HART®.

  • Alarm switches

    SurePoint™ clamp-on switches on the gauge chamber, for high and low alarms.

Ordering

Each GWR assembly is engineered to the vessel and quoted to the datasheet: the gauge by its model code, the radar by its order code, and the chambers, valves and connections on the drawing. The approval drawing is issued after the purchase order.

Selection

Which signal with the gauge

ArrangementSuitsConsider
Gauge aloneLocal readingA level reading at the vessel, with no power.No signal to the control system.
Gauge with SurePoint™ switchesAlarm contactsHigh and low alarms from the gauge.Point alarms, not a continuous level. SurePoint™
Gauge with LevelSync™Magnetostrictive, on the gaugeA continuous signal from the same float, with no second chamber.Gauge and transmitter read one float. LevelSync™
GWRThis pageTwo readings on different principles, total level and interface from one transmitter, or a plant standard for radar.A second chamber and a wetted probe: on a bridle the two instruments share one pair of nozzles; in its own chamber the radar has its own pair.

Enquiry

What to send for a quotation

A complete request is quoted fastest. Send the available details; Lamont Controls Engineering will ask for the rest.

  1. Vessel connectionsNozzle size, flange class and centre-to-centre, and whether one pair or two pairs are available.
  2. Process conditionsFluid, specific gravity, operating and design pressure and temperature; the dielectric constant if known.
  3. InterfaceWhether an interface is to be measured, and the two liquids.
  4. RadarOutput, hazardous area classification, SIL if required, and any preferred make.
  5. GaugeMeasuring range, indicator and scale, and any alarm switches.
  6. Tag numbers and required dateOne request can cover several vessels; give each a tag number.

Upload your datasheets and drawings with the request

Quotation

Request a quotation

Complete the fields below, or attach the datasheet, requisition or tag list: with a file attached, the process fields are optional. Fields marked * are required for pricing.

For several vessels, send one request with a tag number for each, or attach the tag list. For a general enquiry, select Quick message.

What happens nextLamont Controls Engineering reviews the request and replies with a quotation.

1-833-7LAMONT info@lamontcontrols.com

Provide your contact details and a brief message. Lamont Controls Engineering will follow up.

Attach the datasheet, requisition or tag list and enter your contact details. Lamont Controls Engineering takes the process data from the file.

A datasheet, requisition or tag list can replace the process fields: attach it and they become optional.

Contact

Lamont Controls Engineering reviews every request.By sending this form you agree to the Terms of use. See the Privacy policy.

Questions

GWR questions

What is a GWR assembly from Lamont?

A Lamont magnetic level gauge with a guided wave radar transmitter in its own chamber beside it, supplied as one assembly. The gauge reads at the vessel with no power; the radar sends a 4–20 mA signal with HART® to the control system. The two can share one pair of vessel nozzles on a bridle, or the radar can have its own chamber and nozzles.

Does Lamont make the radar transmitter?

No. The radar is a guided wave radar transmitter from an established instrument maker: the standard transmitter Lamont supplies, or the make the plant has standardized on. Lamont supplies the gauge and the chambers, and supplies the radar with the assembly.

Why is the radar not in the gauge chamber?

Each instrument has its own chamber, so the probe stays clear of the float. A float held up by deposits, or a coated probe, affects one reading, not both. With isolation valves, the radar chamber can be shut off and the transmitter removed while the gauge stays in service.

GWR or LevelSync?

LevelSync is a magnetostrictive transmitter that clamps to the gauge chamber and reads the same float as the gauge, with no second chamber. GWR adds a second measurement on a different principle, and one radar can give the total level and the interface together. Choose GWR for two readings on different principles, total level with interface, or a plant standard for radar.

Can it measure an interface?

Yes. The radar can give the total level and the interface when a non-conductive liquid at least 100 mm (4 in) thick sits over a liquid whose dielectric constant is at least 10 higher, such as oil over water, and the two separate cleanly. Interface accuracy is typically ±5 mm. State the two liquids on the request.

What should a request include?

The vessel nozzles (size, class and centre-to-centre), the fluid, specific gravity, operating and design pressure and temperature, whether an interface is to be measured, the radar output, the hazardous area classification and any preferred radar make, and the gauge range. Lamont Controls Engineering replies with a quotation.